IR Speed Dome Installation Manual
19
1.4.3 Baud Rate Settings
The positions 1-3 of the DIP Switch SW2 are used for setting the baud rate of the dome. The values are 100, 010, 110,
respectively representing 2400bps, 4800bps, 9600bps. If the baud rate is out of the above range, it will be the default setting, 2400bps.
Refer to the following table:
DIP Switch SW2-Baud Rate Settings
Baud Rate Positions1-3 Settings 1 2 3
2400
ON
1 2 3 4 5 6 7 8
SW2
ON OFF OFF
4800
ON
1 2 3 4 5 6 7 8
SW2
OFF ON OFF
9600
ON
1 2 3 4 5 6 7 8
SW2
ON ON OFF
1.4.4 Protocol Settings
The positions 4-6 of the DIP Switch SW2 are used for setting the communication protocols of the dome. Refer to the following table
(network speed dome model does not support Manchester code protocol):
DIP Switch SW2-Protocol Settings
Protocol Positions 4-6 Settings 4 5 6
Bosch Manchester
ON
1 2 3 4 5 6 7 8
SW2
OFF ON ON
AD Manchester
ON
1 2 3 4 5 6 7 8
SW2
ON ON ON
Self-adaptive Others
1.4.5 Simplex/Half-duplex Settings
The position 7 of the DIP Switch SW2 is used for setting the communication method of the dome to simplex or half-duplex.
DIP Switch SW2-Simplex/Half-duplex Settings
Description
Position 7 Setting 7
Simplex
ON
1 2 3 4 5 6 7 8
SW2
OFF
Half-duplex
ON
1 2 3 4 5 6 7 8
SW2
ON
1.4.6 Terminal Matched Resistance Settings
The position 8 of the DIP Switch SW2 is used for setting the terminal matched resistance of the dome.
DIP Switch SW2-Terminal Matched Resistance Settings
Description Position 8 Setting 8
Not
Terminated
ON
1 2 3 4 5 6 7 8
SW2
OFF
Terminated
ON
1 2 3 4 5 6 7 8
SW2
ON